Red Tag or Yellow Tag on Your Fire Alarm in Houston or Harris County? What It Means and How to Clear It

A red tag means your fire alarm system, or part of it, is inoperable, has a fault, or is impaired. A yellow tag means the system works but doesn’t comply with code or isn’t being tested and maintained as required. Either way, the licensed company that tagged it must notify the owner and the fire marshal, and the tag stays on until a licensed company makes the corrections and attaches a service label. A red tag on an inoperable system is urgent: the fire marshal can require a fire watch or evacuation until it’s fixed. Need a tag cleared? Call (346) 537-3473 or request service.

The short answer

What does a red tag on a fire alarm mean?

The system or part of it is inoperable, has a fault condition, or is impaired from normal operation, and corrective action is needed (HFD LSB Standard 02 §2.3.2.2; 28 TAC §34.624).

What does a yellow tag on a fire alarm mean?

The system doesn’t comply with applicable codes and adopted standards, or isn’t being tested or maintained according to them (LSB 02 §2.3.2.3; 28 TAC §34.623). It still needs correcting.

Can I take the tag off myself?

No. Only a licensed employee or agent of a registered firm, a State Fire Marshal’s Office employee, or an authorized representative of the Houston Fire Marshal’s Office may remove a red or yellow label, and only after the conditions are corrected and a service label is attached (LSB 02 §§2.3.2.2(d), 2.3.2.3(d)).

Sources: HFD LSB Standard 02, Rev. 05 (effective 01/01/2024), the State Fire Marshal’s fire alarm rules at 28 Texas Administrative Code §§34.623–34.624, the City’s 2021 Fire Code amendments, and the Harris County fire code amendments.

Red tag vs yellow tag

Red tagYellow tag
MeansInoperable, fault condition, or impaired from normal operationDoesn’t comply with codes and standards, or not tested or maintained as required
Typical causesPanel won’t operate, failed notification or detection circuits, communicator or monitoring failure, impaired devicesMissing or wrong devices, overdue testing, code issues that don’t stop the system from working
Notice from the licensed companyInoperable: oral notice to the owner or occupant and the fire marshal immediately, written notice within the next business day. Fault or impaired: written notice within 3 business daysWritten notice within 5 business days
How it comes offCorrections made, service label attached, then removed by an authorized person; fire marshal notified within 5 business daysSame
Where it goesOutside of the control panel cover, or a permanent location if there’s no panelSame

Timelines are from LSB 02 §§2.3.2.2 and 2.3.2.3, which match 28 TAC §§34.623 and 34.624.

What the licensed company must do in Houston

Under HFD LSB Standard 02:

  1. Tag it. If the system doesn’t comply, has a fault, or is impaired, the licensee notifies the owner or owner’s representative and the fire code official, and attaches a yellow or red label in addition to the inspection label (§2.3.2.1(d)).
  2. Notify, on a deadline. For an inoperable system, the licensee or registered firm must orally notify the property owner, occupant, or their representative, and the fire code official when available, immediately after attaching the red label, then follow up in writing within the next business day. For a fault or impairment, written notice is due within 3 business days. For a yellow label, written notice is due within 5 business days (§§2.3.2.2(c), 2.3.2.3(c)).
  3. Leave the tag on until the conditions are corrected and a service label certifies the corrections (§§2.3.2.2(d), 2.3.2.3(d)).
  4. Report the fix. The fire code official must be notified within 5 business days after a red or yellow label is removed or revised (§§2.3.2.2(d), 2.3.2.3(d)).

Servicing and tagging must be done by companies licensed by the State of Texas (LSB 02 §2.3.1).

Harris County: reporting through The Compliance Engine

In unincorporated Harris County, all installations, testing and maintenance, and yellow or red tag notifications must be reported to the fire code official through the online platform approved by Commissioners Court. That report counts as the notice to the fire marshal required by state rules (Harris County Fire Code §109.3.1). The Harris County Fire Marshal’s Office uses The Compliance Engine for this, and requires every service provider that inspects or tests fire protection systems in its jurisdiction to submit its reports there (HCFMO).

How the deficiency cycle works:

  1. The service company submits the report with any deficiencies typed out.
  2. The owner gets notified. HCFMO sends notifications through the platform. A deficiency letter lists what needs correcting.
  3. Corrections are made by a licensed company.
  4. The service company updates the deficiency tracking so HCFMO sees the violations as corrected.

Follow the deadline on your notice. If violations aren’t corrected, the fire marshal can issue a notice of violation or Fire Marshal’s Order with a reinspection date, and in cases of extreme danger immediate compliance is required (Harris County §§112.3, 112.3.2). Correcting violations is the owner’s responsibility (§112.2). Keep records for at least 3 years (§109.3).

Not sure which fire marshal covers your address? See Houston vs Harris County Fire Marshal.

Can I stay open with a red-tagged fire alarm?

It depends on the condition and the fire marshal. When a required fire protection system is out of service, the fire department and the fire code official must be notified immediately. Where the fire code official requires it, the building must be evacuated or an approved fire watch provided for everyone left unprotected until the system is back in service (IFC §901.7). In the City of Houston, the fire code official can also require standby inspectors (Houston §§901.7, 115.1).

  • In Houston, call HFD’s Office of Emergency Communications at 713-884-3143 when a required system goes out of service for emergency or unscheduled repairs, and again when it’s restored. Have the address and building name, your name and number, which system is impaired, and how long it should be out (Houston §901.12; LSB 02 §2.3.6).
  • Fire watch personnel must have at least one approved way to notify the fire department, and their only job is to patrol constantly and watch for fires (IFC §901.7). See fire watch steps.
  • A yellow tag usually doesn’t take the system out of service, but it still has to be corrected.

If the system went down after a storm or outage, see fire alarm hurricane and power outage readiness.

How to clear a red or yellow tag

  1. Read the tag and the written notice. Both list the conditions found. The tag also shows the registered firm’s name and certificate number.
  2. Handle safety first. If the system is inoperable, make the required notifications and set up a fire watch if the fire marshal requires one.
  3. Call a licensed fire alarm company to correct every listed condition. Don’t silence, disconnect, or bypass anything to make troubles go away; tampering with a required system is unlawful (IFC §901.8). See how to silence or reset a fire alarm, and when to call.
  4. Get the service label. Once corrections are made, the company attaches a service label and removes the red or yellow label.
  5. Make sure the fire marshal is told. In Houston, the fire code official is notified within 5 business days of removal. In unincorporated Harris County, the correction goes in through the county’s reporting platform.
  6. Keep the paperwork for at least 3 years (LSB 02 §2.3.5; Harris County §109.3).

What usually leads to a tag

In ASAP’s experience, expired fire alarm inspections and systems that aren’t monitored are common problems on Houston-area properties. Required systems must be monitored (Houston Building Code §901.6.3; Harris County §907.6.6) and tested at least annually (LSB 02 §2.4.1.1). For the full list, see why fire alarm inspections fail.

How ASAP helps

ASAP Fire Protection holds Texas Alarm Certificate of Registration ACR-2949596 and Texas Extinguisher Certificate of Registration ECR-2958332. Our certified, licensed technicians find and correct the conditions on red and yellow tags, attach the service label, and make sure the required notices reach the fire marshal, in the City of Houston and unincorporated Harris County. Sprinkler deficiencies go through our licensed sprinkler partner. For a quick overview, ASAP also runs gotaredtag.com. See fire alarm repair and maintenance, fire alarm inspection, and fire alarm monitoring.

FAQ

What is the difference between a red tag and a yellow tag on a fire alarm?

A red tag means the system or part of it is inoperable, has a fault, or is impaired. A yellow tag means it doesn’t comply with codes and standards or isn’t being tested or maintained as required (LSB 02 §§2.3.2.2, 2.3.2.3; 28 TAC §§34.623, 34.624).

Who notifies the fire marshal about a red tag in Houston?

The licensee or registered firm that attached the tag. For an inoperable system, that’s an immediate oral notice to the owner or occupant and the fire code official when available, then written notice within the next business day. For a fault or impairment, written notice is due within 3 business days (LSB 02 §2.3.2.2(c)).

Can I stay open with a red-tagged fire alarm?

Only as the fire code official allows. When a required system is out of service, the fire department and fire code official must be notified immediately, and the fire code official can require evacuation or a fire watch until the system is restored (IFC §901.7). In Houston, call 713-884-3143 (LSB 02 §2.3.6).

Who can remove a red or yellow fire alarm tag?

A licensed employee or agent of a registered firm, an employee of the State Fire Marshal’s Office, or an authorized representative of the Houston Fire Marshal’s Office, after corrections are made and a service label is attached (LSB 02 §§2.3.2.2(d), 2.3.2.3(d)).

I got a Compliance Engine deficiency letter in Harris County. What do I do?

Have a licensed company correct the listed deficiencies by the deadline on the notice. The company then updates the deficiency tracking in the county’s platform so the Harris County Fire Marshal’s Office sees the violations as corrected (Harris County §109.3.1).

How long do I have to fix a yellow tag?

LSB 02 sets the company’s notice deadlines, not a fixed repair deadline for the owner. The tag stays on until corrections are made. If the fire marshal issues a notice of violation, it will set a time for reinspection. Fix it promptly and keep the records.


Rules change; confirm with your fire marshal or building official. This page is general information, not legal or code advice.

Call (346) 537-3473 or request a quote.

Questions? Call (346) 537-3473 — Monday–Friday, 8:00 AM – 5:00 PM Central. 24/7 Emergency Service.

Houston downtown skyline at dusk

Get a fire protection quote

Licensed Houston technicians for alarms, extinguishers, inspections, and 24/7 emergencies.

Call (346) 537-3473 (346) 537-3473 Get a Quote