Skip to content

Fire Alarm Hurricane and Power Outage Readiness in Houston

When a hurricane or storm knocks out power, your fire alarm runs on its standby batteries, and its monitoring connection has to survive too. If batteries are weak, the communicator depends on a phone line, or a surge damaged the panel, the building can be left without working fire protection exactly when the fire department is stretched thin. Here’s what to check before the season, during an outage, and after the storm. Want a pre-season check? Call (346) 537-3473 or request a free quote.

The short answer

Does a fire alarm work during a power outage?

Yes, for a limited time. Every fire alarm system must have primary and secondary (backup) power that meets NFPA 72 (IFC §907.6.2). For most systems, NFPA 72 sizes the backup batteries to run the system on standby for 24 hours and then operate in alarm for 5 minutes (15 minutes for voice evacuation systems). Longer outages need a generator or a plan.

What should I check on my fire alarm before hurricane season?

The panel shows normal; the batteries are in date and pass their load test; the monitoring communicator reports on its primary and backup paths; surge protection is in place; and every device is accessible. Your annual test covers much of this (LSB 02 §2.4.1.1), so scheduling it before summer is a simple way to start the season clean.

What do I do if the fire alarm is out of service after a storm?

Notify the fire department and fire code official right away. The fire code official can require evacuation or a fire watch until the system is restored (IFC §901.7). In the City of Houston, call HFD’s Office of Emergency Communications at 713-884-3143 when a required system goes out of service for emergency repairs, and again when it’s restored (LSB 02 §2.3.6).

Sources: the City’s 2021 Fire Code amendments, HFD LSB Standard 02, and the Harris County fire code amendments.

Before the season

CheckWhy
Panel shows normal, no trouble or supervisoryA storm won’t fix an existing problem. See alarm, supervisory, or trouble?
Standby batteries in date and load-testedThey carry the system when power fails (IFC §907.6.2; NFPA 72)
Monitoring paths workRequired systems must be monitored (Houston Building Code §901.6.3; Harris County §907.6.6). Copper phone lines often fail in storms. See cellular communicators
Surge protectionUnincorporated Harris County requires surge protection on fire alarm circuits and power (Harris County §907.6.2.1). See thunderstorms and lightning
Emergency lights and exit signsThey need at least 90 minutes on battery (IFC §1008.3.4), with an annual 90-minute test (IFC §1032.10.2). See emergency lighting and exit sign requirements
Fire extinguishersCharged, tagged, and in place (HFD LSB Standard 01 §§1.3.1, 1.3.2)
ContactsMonitoring company, fire alarm company, and after-hours contacts current. In unincorporated Harris County, the key box must hold a list of at least three representatives, with mobile numbers, who can respond to an after-hours emergency (Harris County §506.1)
RecordsLatest inspection report on hand (LSB 02 §2.3.5)

Assisted living and nursing homes in unincorporated Harris County

Harris County requires assisted living facilities (Group I-1) and nursing homes (Group I-2) to have secondary power able to run, at the same time, the fire alarm system (if provided), emergency exit signs and egress lighting, HVAC for resident areas, and other listed systems (Harris County §1203.2.21). Assisted living fire safety and evacuation plans must describe how backup power will be provided within 3 hours of losing electrical service (§§403.7.1.1, 403.7.2.1). Existing facilities must comply before final inspection of an alteration costing more than 50 percent of the building’s appraised value, or approval of a change of occupancy or use (§1103.11). See assisted living fire alarm service.

During an outage

  • Expect a trouble signal. Losing AC power puts the panel in trouble. That’s normal. Don’t silence and forget it.
  • Watch the clock. Batteries are sized for a limited time. If the outage will outlast them and you have no generator on the fire alarm, call your fire alarm company and plan for a fire watch.
  • Keep portable generators outside and away. In unincorporated Harris County, portable generators can’t be stored or run inside the living space, on balconies or patios, or within 10 feet of Group R buildings such as apartments (Harris County §313.2).
  • If the system goes down, notify the fire department and fire code official (IFC §901.7). In Houston, call 713-884-3143 (LSB 02 §2.3.6). See fire watch steps.

After the storm

  1. Check the panel once power is back. Clear conditions should return to normal; anything that stays in trouble needs service.
  2. Confirm monitoring. Ask the monitoring company to confirm they’re receiving signals from your building.
  3. Look for water and wind damage to devices, the panel, and wiring. Water in a device or panel is a service call.
  4. Check the batteries. Deeply drained batteries may not recover and should be load-tested.
  5. Check emergency lights and exit signs with a 30-second test (IFC §1032.10.1).
  6. Check extinguishers that may have been moved, used, or damaged.
  7. Call for service and keep records of what was found and fixed (LSB 02 §2.3.5; Harris County §109.3). In unincorporated Harris County, red or yellow tags go through the county’s reporting platform (§109.3.1).

Not sure which rules apply to your building? See which fire marshal applies to your building.

How ASAP helps

ASAP Fire Protection holds Texas Alarm Certificate of Registration ACR-2949596 and Texas Extinguisher Certificate of Registration ECR-2958332. Before storm season we test fire alarm panels, batteries, and communicators, and after a storm we troubleshoot troubles, restore monitoring, and repair damaged devices, in the City of Houston and unincorporated Harris County. See fire alarm repair, fire alarm monitoring, and emergency light inspection.

FAQ

How long does a fire alarm battery last in a power outage?

Fire alarm systems need secondary power that meets NFPA 72 (IFC §907.6.2). For most systems, NFPA 72 sizes the batteries for 24 hours of standby followed by 5 minutes of alarm (15 minutes for voice evacuation systems). Weak or old batteries won’t last that long.

Why is my fire alarm beeping after a power outage?

Losing AC power and running on batteries puts the panel in trouble. If the trouble doesn’t clear after power returns, the batteries, charger, communicator, or a device may need service. See fire alarm beeping causes.

Will my fire alarm monitoring work if the phone lines are down?

Not if the communicator relies only on copper phone lines. Cellular and other backup communication paths keep monitoring working when phone lines fail. Required systems must be monitored (Houston Building Code §901.6.3; Harris County §907.6.6).

Do I need a fire watch if my fire alarm is down after a hurricane?

The fire department and fire code official must be notified immediately, and the fire code official can require a fire watch or evacuation until the system is restored (IFC §901.7). In Houston, also call HFD at 713-884-3143 (LSB 02 §2.3.6).

Does Harris County require backup power for assisted living?

Yes, in unincorporated Harris County. Assisted living facilities and nursing homes must have secondary power for the fire alarm, exit signs, egress lighting, resident-area HVAC, and other listed systems (Harris County §1203.2.21), and assisted living plans must cover providing backup power within 3 hours (§§403.7.1.1, 403.7.2.1).

Is surge protection required on fire alarms?

In unincorporated Harris County, yes. Fire alarm components needed for initiation and notification must have surge protection, including signaling, notification, telephone, and AC power circuits (Harris County §907.6.2.1).


Rules change; confirm with your fire marshal or building official. This page is general information, not legal or code advice.

Call (346) 537-3473 or request a quote.

Questions? Call (346) 537-3473 — Monday–Friday, 8:00 AM – 5:00 PM Central. 24/7 Emergency Service.