Emergency Lighting and Exit Sign Requirements for Houston Commercial Buildings

Most Houston commercial buildings with two or more exits need exit signs at every exit and emergency lights along the path out, and both must run for at least 90 minutes on backup power. The fire code then requires two tests: a 30-second functional test every month and a full 90-minute battery test every year, with written records. ASAP Fire Protection performs both the monthly checks and the annual 90-minute test. Need your emergency lights inspected? Call (346) 537-3473 or request a free quote.

The short answer

How often do emergency lights and exit signs have to be tested?

Every month for at least 30 seconds, and every year for at least 90 minutes on battery power. That’s the schedule in the 2021 International Fire Code, which the City of Houston and unincorporated Harris County have both adopted (IFC §§1032.10.1, 1032.10.2). NFPA 101, the Life Safety Code, sets the same monthly 30-second and annual 1½-hour tests in §7.9.3.

How long do emergency lights have to stay on?

At least 90 minutes after normal power fails (IFC §1008.3.4). Exit signs also need at least 90 minutes of backup illumination (IFC §1013.6.3).

Do I have to keep records of emergency light tests?

Yes. Emergency lighting must be maintained under the fire code’s maintenance section, which covers recordkeeping (IFC §1032.10). In unincorporated Harris County, inspection and test records must be kept for at least 3 years (Harris County §109.3). NFPA 101 also requires written records of inspections and tests (§7.9.3). Confirm with your fire marshal how they expect the records documented and delivered.

The City publishes its 2021 Fire Code amendments. Harris County publishes its fire code amendments.

Where exit signs are required

Exits and exit access doors must be marked with an approved exit sign that’s readily visible from any direction of travel. Where the exit or the path to it isn’t immediately visible, more signs must show the way (IFC §1013.1).

Exit signs aren’t required (IFC §1013.1, exceptions):

  • In rooms or areas that need only one exit or exit access.
  • At main exterior exit doors that are obviously exits, where the fire code official approves.
  • Inside individual apartments, hotel rooms, and similar dwelling or sleeping units.

Other exit sign rules:

  • Always lit. Exit signs must be internally or externally illuminated and lit at all times (IFC §§1013.3, 1013.5).
  • Listed. Electrically powered, self-luminous, and photoluminescent signs must be listed to UL 924 (IFC §1013.5).
  • Backup power. If normal power fails, sign lighting must continue for at least 90 minutes from batteries, unit equipment, or a generator (IFC §1013.6.3).
  • Hotels. Areas serving guest rooms need additional low-level exit signs (IFC §1013.2).
  • Nothing in the way. Decorations, furnishings, equipment, or nearby signs can’t block an exit sign’s visibility (IFC §1032.4).

Where emergency lighting is required

When normal power fails, emergency lighting has to come on automatically in these areas (IFC §1008.3):

WhereWhat must be lit
Rooms and spaces that need two or more exitsAisles, corridors, and exit access stairways and ramps (§1008.3.1)
Buildings that need two or more exitsInterior exit access stairways and ramps, interior and exterior exit stairways and ramps, exit passageways, exit discharge vestibules and areas, and exterior landings at exit doors (§1008.3.2)
Specific rooms, in any buildingElectrical equipment rooms, fire command centers, fire pump rooms, generator rooms, and public restrooms larger than 300 square feet (§1008.3.3)

How bright and how long. Emergency lighting must start at an average of at least 1 footcandle, with no point below 0.1 footcandle, measured at floor level along the path out. It can fade to 0.6 footcandle average and 0.06 minimum by the end of the 90 minutes (IFC §§1008.3.4, 1008.3.5).

Houston. Inside the city, the equipment that powers egress lighting and exit signs must be kept in operable condition (Houston Fire Code §1008.4).

Unincorporated Harris County. Assisted living facilities (Group I-1) and nursing homes (Group I-2) need secondary power that can run exit signs and egress lighting at the same time as other listed systems (Harris County §1203.2.21). Existing facilities must comply before final inspection of a major remodel or a change of occupancy (§1103.11).

The monthly and annual tests

TestHow oftenWhat happensCode
Functional testEvery monthEach emergency light and lighted exit sign is switched to battery for at least 30 seconds to confirm it comes on. Units with automatic self-testing still need a monthly visual check for trouble lights or damage.IFC §1032.10.1; NFPA 101 §7.9.3
Full-duration testEvery yearBattery-powered units run on battery for at least 90 minutes (1½ hours) and must stay lit for the whole test.IFC §1032.10.2; NFPA 101 §7.9.3
RecordsEvery testWritten record of each inspection and test, kept for the fire code official.IFC §1032.10; NFPA 101 §7.9.3; Harris County §109.3 (3 years)

Confirm with your fire marshal what documentation they expect for monthly and annual tests.

Generators. If your emergency lighting runs on a generator instead of batteries, the generator has its own testing schedule under the fire code’s emergency and standby power rules.

Assisted living and other licensed facilities

Texas requires licensed assisted living facilities to comply with NFPA 101, the Life Safety Code, 2012 edition (26 TAC §553.100; HHSC PL 2021-32). That includes the §7.9.3 emergency lighting tests and written records. HHSC also lists emergency lighting and exit signs as life safety systems for backup-power purposes in large assisted living facilities (HHSC TM 2025-01). See fire protection for assisted living.

Common emergency lighting and exit sign problems

In ASAP’s experience, exit signs that haven’t been tested or don’t work are one of the problems we find most often in Houston-area commercial buildings. Others that fail an inspection:

  • Batteries that die before 90 minutes. The unit lights up for the 30-second check but goes dark partway through the annual test (IFC §1032.10.2).
  • Burned-out lamps or dark exit signs. Exit signs must be lit at all times (IFC §1013.5).
  • Self-test units showing a trouble light that nobody checked (IFC §1032.10.1).
  • No monthly records, or no record of the annual test (IFC §1032.10).
  • Exit signs blocked by decorations, displays, or new signage (IFC §1032.4).
  • Missing signs or lights after a remodel, such as a new corridor or a restroom over 300 square feet with no emergency light (IFC §§1008.3, 1013.1).

Repairs, replacements, and electrical work

A unit that fails the monthly or annual test needs a new battery, lamp, or replacement fixture, then a retest, and the fix goes in your records. Wiring changes or new circuits are electrical work, handled under your local electrical code and permits.

How ASAP helps

ASAP Fire Protection performs emergency light and exit sign inspections across the City of Houston and unincorporated Harris County, including the monthly 30-second checks and the annual 90-minute full-duration test, and we document each test for your records. We can put emergency lights on the same schedule as your fire alarm inspection and fire extinguisher inspection, so you have one set of records. We work with offices, apartments, assisted living, daycares, restaurants and retail, and hotels. Not sure which rules apply? See which fire marshal applies to your building.

FAQ

How often do emergency lights need to be tested?

Monthly for at least 30 seconds, and annually for at least 90 minutes on battery power (IFC §§1032.10.1, 1032.10.2, as adopted by Houston and Harris County). NFPA 101 §7.9.3 sets the same schedule.

What is the 90-minute emergency light test?

Once a year, battery-powered emergency lights and exit signs are run on battery for at least 90 minutes to prove they stay lit for the full time required if the power fails (IFC §1032.10.2; IFC §1008.3.4).

Do exit signs have to be lit all the time?

Yes. Exit signs must be illuminated at all times and must stay lit for at least 90 minutes after a power loss (IFC §§1013.5, 1013.6.3).

Where are emergency lights required?

Where a room or building needs two or more exits: aisles, corridors, exit stairways and ramps, exit passageways, and exterior landings at exit doors. Also in electrical rooms, fire pump and generator rooms, fire command centers, and public restrooms larger than 300 square feet (IFC §1008.3).

Do I need to keep emergency light test records?

Yes. Keep written records of the monthly and annual tests (IFC §1032.10; NFPA 101 §7.9.3). In unincorporated Harris County, records must be kept at least 3 years (Harris County §109.3). Confirm with your fire marshal what documentation they expect.

Do self-testing emergency lights still need monthly checks?

Yes. Self-testing units can run the monthly 30-second test automatically, but someone still has to look at each unit monthly for a trouble indicator or damage (IFC §1032.10.1).


Rules change; confirm with your fire marshal or building official. This page is general information, not legal or code advice.