How to Silence or Reset a Commercial Fire Alarm, and When to Call a Licensed Company

Treat every fire alarm as real until you know otherwise: get people out and call 911. Silencing a commercial fire alarm only stops the horns and strobes; the alarm is still active. Resetting clears it, and should only happen after the fire department has checked the building or you’ve confirmed with your monitoring company that there’s no fire. If the panel won’t reset, keeps going back into alarm, or shows trouble, call a licensed fire alarm company. Need help now? Call ASAP at (346) 537-3473 or request service.

The short answer

What should I do when a commercial fire alarm goes off?

Evacuate, call 911 if there is any sign of fire or you don’t know the cause, and call your monitoring company. Don’t silence or reset the panel to “make it stop” before you know why it went off.

What’s the difference between silencing and resetting a fire alarm?

  • Silence turns off the horns, strobes, or voice message. The panel stays in alarm, and the alarm is still recorded and reported.
  • Reset returns the panel to normal. If the device that caused the alarm still senses smoke or heat, or a pull station is still pulled, the panel goes right back into alarm.

How do I silence or reset my fire alarm panel?

Use the silence and reset steps in the operating instructions for your specific panel, usually posted at or inside the panel. Most panels keep these controls behind a locked door or key switch so only authorized people can use them. If you don’t have instructions or authorization, call your monitoring company and a licensed fire alarm company.

The safe order of steps

  1. Evacuate. Follow your fire safety and evacuation plan.
  2. Call 911 if you see or smell smoke or fire, or you can’t confirm the cause.
  3. Call your monitoring company. Tell them what’s happening. They can tell you what they received (alarm, supervisory, or trouble) and which device, if your system reports by device.
  4. Write down what the panel says: the time, the message, the zone or device, and the type of signal.
  5. Let the fire department clear the building when they respond. Follow their direction on silencing and resetting.
  6. Silence, then reset, using your panel’s instructions, only once the cause is known and the building is cleared.
  7. Call a licensed fire alarm company if the alarm returns, the panel won’t reset, a device is damaged, or the cause isn’t clear.

When you must call a licensed company

Call ASAP or your fire alarm company when:

What not to do

  • Don’t disable, disconnect, or bypass anything. It’s unlawful to remove, tamper with, or otherwise disturb a required fire protection or life safety system, except for the limited purposes the code lists, such as extinguishing a fire, recharging, or making necessary repairs, or where the fire code official approves (IFC §901.8). Removing batteries, unplugging the panel, or covering devices to stop alarms puts people at risk and can bring a citation.
  • Don’t leave the system silenced. A silenced panel isn’t protecting the building the way it should.
  • Don’t take a system out of service without notice. When a required system is out of service, the fire department and fire code official must be notified immediately, and the fire code official can require evacuation or a fire watch (IFC §901.7). In the City of Houston, call HFD’s Office of Emergency Communications at 713-884-3143 when a system is placed out of service for emergency or unscheduled repairs, and again when it’s restored (HFD LSB Standard 02 §2.3.6). See fire watch steps.
  • Don’t cancel monitoring to stop calls. For required systems, the monitoring provider must notify the fire code official in writing when monitoring is terminated (IFC §901.9).

Rules about silence and reset controls

  • Unincorporated Harris County: only one fire alarm system is allowed per building, and multiple points of silence and reset are prohibited, except at the fire alarm control unit and the required annunciator at the main entrance (Harris County Fire Code §§907.2, 907.5.1). On voice systems, the voice instructions keep playing until the system is silenced or reset (§907.5.2.2).
  • City of Houston: the system must be kept operable (IFC §901.6), tested at least annually (LSB 02 §2.4.1.1), and serviced by a company licensed by the State of Texas (LSB 02 §2.3.1).

Sources: the City’s 2021 Fire Code amendments, HFD LSB Standard 02, and the Harris County fire code amendments.

Before the next alarm

  • Post the panel’s operating instructions at the panel, and know who on site is authorized to use them.
  • Keep your monitoring company’s number and account information at the panel.
  • Keep the panel key where authorized staff can get to it.
  • Fix the cause of false alarms so staff don’t start ignoring the alarm.
  • Stay current on testing. See fire alarm testing in Houston and why fire alarm inspections fail.

How ASAP helps

ASAP Fire Protection holds Texas Alarm Certificate of Registration ACR-2949596. We troubleshoot panels that won’t reset, track down false alarms and trouble signals, restore monitoring, and repair devices in the City of Houston and unincorporated Harris County. See fire alarm repair and maintenance, common fire alarm repairs, and fire alarm monitoring.

FAQ

How do I turn off a commercial fire alarm?

Evacuate and call 911 if there’s any chance of fire, then call your monitoring company. Once the cause is known and the building is cleared, silence and reset the panel using the operating instructions for your panel. If it won’t reset or keeps alarming, call a licensed fire alarm company.

What is the difference between alarm silence and reset?

Silence stops the horns, strobes, or voice message, but the panel stays in alarm. Reset returns the panel to normal, and it goes back into alarm if the device that caused it is still active.

Why won’t my fire alarm panel reset?

Usually because a device is still active, such as a detector that still senses smoke or dust, a pull station that hasn’t been reset, or a sprinkler flow or supervisory condition. Call a licensed fire alarm company to find the cause.

Can I disconnect my fire alarm to stop false alarms?

No. It’s unlawful to tamper with or disturb a required fire protection system except for limited purposes such as extinguishing a fire, recharging, or necessary repairs, or where the fire code official approves (IFC §901.8). Call a licensed company to fix the cause.

Who do I call when the fire alarm goes off and there’s no fire?

Call your monitoring company first so they can update the fire department, then call your fire alarm company to find and fix the cause. If you’re not sure there’s no fire, call 911 and evacuate.

Do I have to notify the fire department if my fire alarm is out of service?

Yes. When a required system is out of service, the fire department and fire code official must be notified immediately (IFC §901.7). In Houston, call HFD at 713-884-3143, and call again when the system is restored (LSB 02 §2.3.6).


Rules change; confirm with your fire marshal or building official. This page is general information, not legal or code advice.

Call (346) 537-3473 or request a quote.

Questions? Call (346) 537-3473 — Monday–Friday, 8:00 AM – 5:00 PM Central. 24/7 Emergency Service.

Houston downtown skyline at dusk

Get a fire protection quote

Licensed Houston technicians for alarms, extinguishers, inspections, and 24/7 emergencies.

Call (346) 537-3473 (346) 537-3473 Get a Quote