Kitchen Hood Fire Suppression Inspections in Houston: The Every-6-Months Rule and What Gets Checked

In Houston, the fire suppression system over a commercial cooking hood, often called an Ansul system, must be inspected and service-tagged at least every 6 months and after any time it discharges. An approved fire protection equipment company has to do the work, following the manufacturer’s guidelines and NFPA 17 and 17A. The Class K extinguisher in the kitchen needs its own annual inspection and tag. ASAP inspects restaurant hood suppression systems in Houston, either with our own team or through a licensed partner. Need your 6-month hood inspection? Call (346) 537-3473 or request a quote.

The short answer

How often does a restaurant hood suppression system need to be inspected in Houston?

At least every 6 months, and after any activation, by an approved fire protection equipment company (HFD LSB Standard 02 §2.9.1). The fire code has the same 6-month interval and requires a certificate of inspection to be sent to the fire code official (IFC §904.13.5.2).

What standard does the inspection follow?

The system manufacturer’s guidelines, plus NFPA 17 (dry chemical) and NFPA 17A (wet chemical), as LSB 02 §2.9.1 requires. Most restaurant systems today are wet chemical.

Does the system have to meet UL 300?

Yes. LSB 02 §2.9.1 notes that under state regulation, all commercial kitchen hood fire protection systems have had to meet UL 300 since January 1, 2008. The fire code also requires pre-engineered wet- and dry-chemical systems to be tested to UL 300 and listed for the use (IFC §904.13).

Is the Class K extinguisher part of the hood inspection?

It’s checked separately. Class K extinguishers in commercial kitchens must be inspected, tested, service-tagged, and maintained every year under NFPA 10 and 17 (LSB 02 §2.9.2).

Sources: HFD LSB Standard 02, Rev. 05 (effective 01/01/2024), the City’s 2021 Fire Code amendments, and HFD LSB Standard 01, Rev. 05 (portable fire extinguishers).

What a kitchen hood suppression system is

A pre-engineered system mounted in and above the hood. It has:

  • Detection: fusible links or heat detectors in the hood and at the duct opening that react to fire temperatures.
  • Agent and piping: a tank of wet-chemical agent (or dry chemical on some older or special systems) piped to nozzles aimed at the appliances, the hood plenum, and the duct.
  • Manual pull station: required at or near a means of egress from the cooking area, 10 to 20 feet from the exhaust system and 42 to 48 inches above the floor (IFC §904.13.1).
  • Shutoffs: when the system discharges, it must automatically shut off fuel or electric power to the cooking equipment it protects, and the reset must be manual (IFC §904.13.2).
  • Fire alarm tie-in: where the building has a fire alarm system, the suppression system must be monitored by it under NFPA 72 (IFC §904.3.5).

People often call these Ansul systems after a well-known product line, but many manufacturers make them. The 6-month rule applies whatever the brand.

What an Ansul system inspection covers

Whatever the brand, the 6-month inspection follows the manufacturer’s manual for your system and NFPA 17A (or NFPA 17 for dry chemical). A typical semiannual inspection includes:

  • Hazard check: confirming the appliances under the hood still match what the system was designed for. Moving, adding, or swapping cooking equipment, or changing the cooking medium, can mean the system has to be brought back into compliance (IFC §904.13.5.1).
  • Nozzles: in the right place, aimed at the right appliances, clean, and capped.
  • Detection line: fusible links or detectors checked and replaced on schedule. The fire code requires fusible links to be replaced at least once a year (IFC §904.13.5.3), and NFPA 17A calls for replacing them more often, so they’re commonly changed at the 6-month service. When links are due, ASAP replaces them as part of the inspection visit.
  • Agent and cylinders: agent level and pressure in range, the cylinder date checked, and no damage or corrosion.
  • Operation test: the detection system, release mechanism, and manual pull station tested without discharging agent.
  • Shutoffs and interlocks: gas valve or electric shunt trip operates, and the fire alarm connection signals where one is required.
  • Hood and duct: the inspector notes heavy grease buildup. LSB 02 §2.9.1 requires hoods, ducts, exhaust fans, and related parts to be cleaned and inspected as often as needed to prevent excess grease. That cleaning is done by a hood cleaning company.
  • Tag and report: a new service tag on the system and a written report. Keep records for at least 3 years (LSB 02 §2.3.5).

If something doesn’t pass, the report lists what needs correcting before the system can be tagged as compliant.

After a discharge

If the hood system goes off, whether for a real fire or by accident, it has to be serviced and re-tagged before you cook under that hood again (LSB 02 §2.9.1; IFC §904.13.5.2). The fuel or power to the appliances stays off until it’s manually reset. If the discharge also set off the building fire alarm, the alarm needs to be reset and checked too. See how to silence or reset a commercial fire alarm.

Class K extinguishers and the rest of the kitchen

  • Where: a listed Class K extinguisher must be within 30 feet of commercial cooking equipment that uses vegetable or animal oils and fats, measured along a clear path (HFD LSB Standard 01 §1.5.1; IFC §906.1).
  • How many for fryers: one Class K extinguisher of at least 1.5 gallons for up to four fryers holding up to 80 pounds of cooking oil each, plus one more for each additional group of four. Larger fryers follow the extinguisher manufacturer’s recommendations (IFC §906.4.2).
  • Order of use: the hood system is the main protection. A Class K extinguisher is meant to be used after the hood system has discharged, and a placard near it usually says so.
  • Annual service: Class K extinguishers are inspected, tested, and tagged every year (LSB 02 §2.9.2). See fire extinguisher inspection.
  • The rest of the building: dining rooms and back-of-house still need ABC extinguishers sized for the space. See what size fire extinguisher does my Houston business need?
  • Food trucks: mobile kitchens have their own rules. See food truck extinguisher requirements.

Who can inspect a kitchen hood system in Houston?

LSB 02 §2.9.1 says an “approved fire protection equipment company,” and the fire code requires inspection by qualified individuals (IFC §904.13.5.2). Keep a copy of every inspection report and make sure the current service tag stays on the system.

If your restaurant is in unincorporated Harris County, the county fire marshal’s rules apply instead. See Houston vs. Harris County fire marshal.

How ASAP helps

ASAP Fire Protection holds Texas Extinguisher Certificate of Registration ECR-2958332 and Texas Alarm Certificate of Registration ACR-2949596. We handle your 6-month kitchen hood suppression (Ansul system) inspections. Each one is performed by ASAP’s team or by a licensed partner, with a tag and written report for your records. When fusible links are due, we replace them as part of the service. At the same visit we can handle your Class K and ABC fire extinguisher inspections, and test the hood system’s connection to your fire alarm during your annual fire alarm inspection. One visit can also cover your emergency lights. See life safety inspection. For everything else we do as a Houston fire protection company, call (346) 537-3473.

FAQ

How often does an Ansul system need to be inspected in Houston?

At least every 6 months and after any discharge. That goes for any kitchen hood fire suppression system, whatever the brand. The inspection must be done by an approved fire protection equipment company, following the manufacturer’s guidelines and NFPA 17 and 17A (LSB 02 §2.9.1).

What is checked during an Ansul system inspection?

Whether the appliances still match the system design, nozzle placement and caps, fusible links or detectors, agent cylinders and pressure, the release mechanism and manual pull station, the gas or electric shutoff, and the fire alarm connection. The system is then tagged and you get a written report.

The fire code requires fusible links to be replaced at least once a year (IFC §904.13.5.3). NFPA 17A calls for more frequent replacement, so they’re commonly changed at the 6-month service. Follow your system’s manual and your inspector’s report. ASAP replaces fusible links during the inspection when they’re due.

Does my hood suppression system have to be connected to the fire alarm?

If the building has a fire alarm system, yes. The suppression system must be monitored by it under NFPA 72 (IFC §904.3.5).

What happens if my hood system discharges?

The gas or electric supply to the cooking equipment shuts off and stays off until it’s manually reset (IFC §904.13.2). The system must be serviced and re-tagged before you cook under that hood again (LSB 02 §2.9.1).

Do I still need a Class K fire extinguisher if I have a hood system?

Yes. A listed Class K extinguisher is required within 30 feet of commercial cooking equipment that uses oils and fats (LSB 01 §1.5.1; IFC §906.1). It’s used after the hood system discharges, and it’s inspected and tagged every year (LSB 02 §2.9.2).

Is hood cleaning the same as a hood suppression inspection?

No. Hood cleaning removes grease from the hood, ducts, and fan, as often as needed to prevent buildup (LSB 02 §2.9.1). The suppression inspection checks the fire system. You need both.


Rules change; confirm with your fire marshal or building official. This page is general information, not legal or code advice.